GRH 40÷450
Heat Recovery Unit from 380 to 4.500 m³/h with VERY HIGH EFFICIENCY exchanger




A ventilation unit designed and manufactured for non-residential applications allows combining the need for air renewal with maximum energy saving. Equipped with a counterflow heat recovery unit in aluminium plates, it specifically meets the requirements of EU Regulation no. 1253/2014. By nature, they are units that generally tend to integrate with traditional heating/air conditioning systems, even if, equipped with the appropriate accessories, they can be used completely on their own. The series, both in horizontal and vertical set-up, is divided into six sizes, for air flow rates ranging from 380 to 4500 m³/h.
Versions
- GRH/HA - Horizontal installation A type configuration
- GRH/HB - Horizontal installation B type configuration
- GRH/VC - Vertical installation C type configuration
- GRH/VD - Vertical installation D type configuration
Features
- The structure is made with 25 mm thick insulated panels in galvanised sheet metal on the inside and RAL 9002 pre-painted finish on the outside, internally insulated with non-flammable mineral wool thermal-acoustic insulation.
- Compact filters with synthetic media (external layer) and glass fibre media (internal layer) and galvanised steel frame, in the efficiency class ePM10 50% on the ambient air intake and ePM1 50% on the outdoor air intake, removable on the bottom. Each filtering station is already equipped with a control pressure switch wired on board and suitable to house two filters in sequence.
- EC Inverter Plug-Fans.
- The high-efficiency heat recovery unit is of the air-to-air counterflow flow type with aluminium exchange plates with an integrated by-pass system for free-cooling operation.
- Electrical board built-in in the unit with electronic adjustment and remote user interface for complete control of all features: ventilation and temperature control, filter status monitoring, weekly programming, defrost and antifreeze management, fire alarm management and Modbus interface.
Accessories
Factory fitted accessories
- FTF9 Plate filters efficiency F9 ePM1 85% - Second stage
- AT Constant air flow regulation control
- EHP Supplementary electrical heater-PRE
- EHR Supplementary electrical heater-POST
Loose accessories
- CRT Touch screen remote control panel
- PMM Multidirectional plenum
- BCF Nozzle for circular ducts - Frontal
- BCL Nozzle for circular ducts - Lateral
- SK1 Adjustment damper - Frontal
- SK2 Adjustment damper - Lateral
- SM Servo-motor for damper
- GA1 Anti-vibrating joint - Frontal
- GA2 Anti-vibrating joint - Lateral
- WFH Water cooling / heating section - Horizontal
- WFV Water cooling / heating section - Vertical
- WXH Direct expansion cooling / heating section - Horizontal
- WXV Direct expansion cooling / heating section - Vertical
- SQO Air quality probe (Co2)
- KSA Sanitization module with UVC plasma and antivirus
- V33 3-way modulating valve with servo control
- TTH Roof covering - Horizontal
- TTV Roof covering - Vertical
- TTA Roof covering for WFH and WXH - Horizontal
- TTB Roof covering for WFV and WXV - Vertical
Technical data
40 | 70 | 115 | 170 | 250 | 330 | 450 | |||
Air flow | Nominal | m³/s | 0,11 | 0,20 | 0,31 | 0,48 | 0,68 | 0,92 | 1,25 |
Sound pressure | Sound pressure (1) | dB(A) | 54 | 53 | 51 | 59 | 59 | 60 | 64 |
Electrical characteristics | Power supply | V/Ph/Hz | 230/1/50-60 | 230/1/50-60 | 230/1/50-60 | 230/1/50-60 | 400/3+N/50-60 | 400/3+N/50-60 | 400/3+N/50-60 |
Motors nominal power | kW | 0,34 | 0,34 | 0,73 | 0,93 | 1,65 | 1,92 | 3,05 | |
Rated operating current | A | 2,8 | 2,9 | 5,0 | 6,0 | 2,9 | 3,4 | 4,8 | |
Max. running current | A | 2,8 | 2,9 | 6,0 | 6,0 | 3,4 | 3,5 | 7,6 | |
Max. motor power | kW | 0,34 | 0,34 | 0,92 | 0,93 | 2,00 | 2,00 | 4,85 | |
OPERATING RANGE | Max. air flow imbalance | % | 30 | 30 | 30 | 30 | 30 | 30 | 30 |
Min air temperature | °C | -20 | -20 | -20 | -20 | -20 | -20 | -20 | |
Max air temperature | °C | 45 | 45 | 45 | 45 | 45 | 45 | 45 | |
Heat Recovery | Recovery efficiency (2) | % | 92,1 | 91,7 | 91,7 | 91,5 | 90,7 | 90,8 | 91,3 |
Recovery capacity (2) | kW | 3,5 | 6,6 | 10,5 | 15,6 | 22,3 | 29,9 | 35,2 | |
Delivery temperature (2) | °C | 17,6 | 17,5 | 17,5 | 17,5 | 17,2 | 17,2 | 17,1 | |
Compliance with EU Regulation 1253/2014 | Recovery efficiency (3) | % | 83,8 | 82,8 | 82,4 | 82,0 | 81,4 | 81,5 | 82,9 |
Efficiency bonus | W/m³/s | 324 | 294 | 282 | 270 | 252 | 255 | 297 | |
Filter correction factor | 0 | 0 | 0 | 0 | 0 | 0 | 0 | ||
Internal SFP limit | W/m³/s | 1408 | 1364 | 1335 | 1299 | 1249 | 1217 | 1209 | |
Internal SFP | W/m³/s | 1403 | 1301 | 1319 | 1183 | 1219 | 1213 | 992 | |
Electrical heater | Heating capacity | kW | --- | --- | --- | --- | --- | --- | --- |
Power supply | V/Ph/Hz | 230/1/50 | 230/1/50 | 230/1/50 | 230/1/50 | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 | |
Water cooling/heating section | Total cooling capacity (4) | kW | 2,46 | 4,47 | 6,65 | 10,62 | 16,14 | 20,68 | 26,29 |
Sensible cooling capacity (4) | kW | 1,35 | 2,41 | 3,66 | 5,84 | 8,72 | 11,37 | 14,20 | |
Heating capacity (5) | kW | 3,30 | 5,86 | 9,08 | 12,97 | 20,83 | 27,50 | 33,36 | |
Water flow (4) | l/s | 432 | 756 | 1152 | 1836 | 2772 | 3564 | 4500 | |
Water-side pressure drops (4) | kPa | 12 | 18 | 9 | 13 | 19 | 15 | 33 | |
Air-side pressure drops (4) | Pa | 51 | 53 | 51 | 46 | 50 | 55 | 54 | |
Water connections | " G | 3/4 | 3/4 | 3/4 | 3/4 | 3/4 | 1 | 1 | |
Weight | kg | 28 | 31 | 35 | 42 | 52 | 58 | 77 | |
Weights | Transport weight | kg | 99 | 120 | 199 | 263 | 326 | 405 | 549 |
Operating weight | kg | 86 | 106 | 181 | 237 | 297 | 367 | 520 |
Dimensions
40 | 70 | 115 | 170 | 250 | 330 | 450 | |||
L | HA-HB | mm | 1350 | 1470 | 1850 | 1850 | 2150 | 2150 | 2350 |
VC-VD | mm | 1350 | 1470 | 1850 | 1850 | 2150 | 2150 | 2350 | |
W | HA-HB | mm | 680 | 820 | 1030 | 1460 | 1460 | 1840 | 1900 |
VC-VD | mm | 330 | 370 | 455 | 455 | 590 | 590 | 800 | |
H | HA-HB | mm | 330 | 370 | 455 | 455 | 590 | 590 | 800 |
VC-VD | mm | 680 | 820 | 1030 | 1460 | 1460 | 1840 | 1900 |
Notes
- 1 Outdoor air circuit side/supply at nominal air flow and 1 m from the unit.
- 2 Under humid conditions at nominal flow rate: outdoor air at - 10 °C 90% RH, ambient air at 20 °C 60% RH.
- 3 Under dry conditions at nominal flow rate: outdoor air at 5°C, ambient air at 25°C.
- 4 At nominal flow rate: air in/out at 28° C 60% RH, water in/out at 7°/12° C.
- 5 At nominal flow rate: air in/out at 13° C 60% RH, water in/out at 45°/40° C.